Sign In | Join Free | My himfr.com |
|
Ask Lasest Price | |
Brand Name : | IFM |
Model Number : | PN3071 |
Certification : | CE |
Price : | USD |
Payment Terms : | L/C, T/T |
Supply Ability : | 100 |
Delivery Time : | 10-12Days |
IFM Pressure sensor with display PN3071 PN-250-SER14-MFRKG/US/ /V
The IFM PN3071 PN-250-SER14-MFRKG/US/V is a pressure sensor with a display, manufactured by IFM Electronic GmbH. Here's some information about the pressure sensor:
1. Model: PN3071 PN-250-SER14-MFRKG/US/V
2. Manufacturer: IFM Electronic GmbH
3. Function: The pressure sensor is designed to measure and monitor
pressure levels in industrial applications.
4. Display: The sensor features a built-in display that allows for
convenient on-site pressure reading and monitoring. The display
typically shows the measured pressure value in the desired unit of
measurement.
5. Pressure Range: The pressure range supported by the sensor
depends on the specific model variant. In this case, the "PN-250"
in the model name suggests a pressure range up to 250 bar. However,
it's always recommended to refer to the product documentation or
datasheet for the exact pressure range of this particular model.
6. Electrical Connection: The sensor supports a specific electrical
connection type, indicated by the "/US" in the model name. The
exact type of electrical connection may vary, and you should
consult the product documentation or datasheet for more details.
7. Process Connection: The sensor has a process connection suitable
for the application. The specific process connection type can be
identified by the "/V" in the model name. Again, referring to the
product documentation will provide precise information about the
process connection.
For detailed specifications, installation guidelines, and compatibility information for the IFM PN3071 PN-250-SER14-MFRKG/US/V pressure sensor with display, it is recommended to consult the official documentation provided by IFM Electronic GmbH or contact their technical support. They will be able to provide you with accurate and up-to-date information based on your specific requirements and the latest product information available.
Product characteristics
Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 | |||
Measuring range |
| |||
Process connection | threaded connection G 1/4 internal thread M6 I |
Application
Special feature | Gold-plated contacts | |||
Measuring element | metallic thin film cell | |||
Application | for industrial applications | |||
Media | liquids and gases | |||
Medium temperature [°C] | -25...80 | |||
Min. bursting pressure |
| |||
Pressure rating |
| |||
Vacuum resistance [mbar] | -1000 | |||
Type of pressure | relative pressure |
Electrical data
Operating voltage [V] | 18...30 DC; (to SELV/PELV) |
Current consumption [mA] | < 35 |
Min. insulation resistance [MΩ] | 100; (500 V DC) |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | < 0.3 |
Integrated watchdog | yes |
Inputs / outputs
Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
Outputs
Total number of outputs | 2 |
Output signal | switching signal; analogue signal; IO-Link; (configurable) |
Electrical design | PNP |
Number of digital outputs | 1 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 150; (200 (...60 °C) 250 (...40 °C)) |
Switching frequency DC [Hz] | < 170 |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4...20 |
Max. load [Ω] | 500 |
Analogue voltage output [V] | 0...10 |
Min. load resistance [Ω] | 2000 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range
Measuring range |
|
Factory setting / CMPT = 2
Set point SP |
| |||
Reset point rP |
| |||
Min. difference between SP and rP |
| |||
In steps of |
|
Status_B High Resolution / CMPT = 3
Set point SP |
| |||
Reset point rP |
| |||
Min. difference between SP and rP |
| |||
In steps of |
|
Accuracy / deviations
Switch point accuracy [% of the span] | < ± 0,5 |
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) |
Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
Hysteresis deviation [% of the span] | < ± 0,25 |
Long-term stability [% of the span] | < ± 0,05; (per 6 months) |
Temperature coefficient zero point [% of the span / 10 K] | 0,2; (-25...80 °C) |
Temperature coefficient span [% of the span / 10 K] | 0,2; (-25...80 °C) |
![]() |